Detection, Removal, and Prevention of Water in Thermal Oil Systems

2022-05-13 03:59:42 By : Mr. Yang Edward

We use cookies to enhance your experience. By continuing to browse this site you agree to our use of cookies. More info.

A best practice before starting up a new thermal oil system is to take a sample from a low point drain into a glass jar. A murky sample indicates the presence of water in the fluid which has to be eliminated by performing a system boilout. A rust colored or clear layer at the bottom of the jar indicates pure water. The time required to thoroughly boilout the system can be reduced by draining the excess water from some of or all the low point drains.

An important point to be noted here is that even if water is not seen in the sample, some amount of residual water might be hidden in the system.

Upon conversion to water vapor, the volume of water is expanded to more than 1100 times, making it highly impossible to be ignored in a closed-loop thermal fluid system.

Following are some of the indicators for the presence of water:

Water remaining in the thermal oil system is not purged out when the system is operated at low heat until stabilization of the pump pressure. Conversely, the residual water is only relocated to the bottom of the expansion tank. Therefore, the sole method by which water can be entirely removed is by forcing it to flash off as water vapor through the vent of the expansion tank.

It is important to note that in the case of a severely contaminated thermal oil system, it is advisable to completely replace the fluid. Although this process may not avoid the need for a boilout, it can minimize the needed time.

Below are some of the points to be followed for rapidly performing boilout of a system:

Invariably, water contamination is mostly self- inflicted. Therefore, the following points should be followed for preventing contamination by water.

This information has been sourced, reviewed and adapted from materials provided by Paratherm.

For more information on this source, please visit Paratherm.

Please use one of the following formats to cite this article in your essay, paper or report:

Paratherm. (2021, March 10). Detection, Removal, and Prevention of Water in Thermal Oil Systems. AZoM. Retrieved on May 12, 2022 from https://www.azom.com/article.aspx?ArticleID=12861.

Paratherm. "Detection, Removal, and Prevention of Water in Thermal Oil Systems". AZoM. 12 May 2022. <https://www.azom.com/article.aspx?ArticleID=12861>.

Paratherm. "Detection, Removal, and Prevention of Water in Thermal Oil Systems". AZoM. https://www.azom.com/article.aspx?ArticleID=12861. (accessed May 12, 2022).

Paratherm. 2021. Detection, Removal, and Prevention of Water in Thermal Oil Systems. AZoM, viewed 12 May 2022, https://www.azom.com/article.aspx?ArticleID=12861.

we have HTF with water mixed during the operation from heat exchanger. Normally any hydrocarbon fluid is at top and water is in bottom. What about HTF water at bottom or top? How much water observe in PPM naturally? What is the acceptable limit of PPM in HTF? Did HTF get contaminated with water dew to humidity if its standing in tank for week or more?

The opinions expressed here are the views of the writer and do not necessarily reflect the views and opinions of AZoM.com.

Do you have a question you'd like to ask regarding this article?

AZoM speaks with Dr. Nicola Ferralis from MIT about his research that has developed a low-cost process of creating carbon fibers from hydrocarbon pitch. This research could lead to the large-scale use of carbon fiber composites in industries that have thus far been limited.

In this interview, AZoM speaks with Marco Enger, Senior Tribologist from GGB, to discuss how nano fillers affect transfer films within tribological systems.

Ahead of their talk on green chemistry and profitability in laboratory research at ChemUK 2022, AZoM spoke with Jacqueline Balian from Gambica and Martyn Fordman from Asynt about encouraging sustainability in the chemical industry.

COXEM's CP-8000+ is a powerful cross section polishing tool that uses an argon ion beam to allow precise, advanced sample preparation. Its state-of-the-art technology means the sample is not deformed and does not suffer any kind of physical damage.

This product profile outlines the Evolution™ Pro UV-Vis Spectrophotometers from Thermo Fisher Scientific.

Extrel’s all-new MAX300-RTG 2.0 is the real-time industrial gas analyzer now redesigned with a touch screen.

AZoM.com - An AZoNetwork Site

Owned and operated by AZoNetwork, © 2000-2022